{"id":896,"date":"2026-07-10T03:28:34","date_gmt":"2026-07-10T03:28:34","guid":{"rendered":"https:\/\/www.gltyelectric.com\/?p=896"},"modified":"2026-07-10T04:59:13","modified_gmt":"2026-07-10T04:59:13","slug":"dc-busbar-vs-cable-data-center-ess","status":"publish","type":"post","link":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/","title":{"rendered":"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS?"},"content":{"rendered":"\n<h2 class=\"wp-block-heading\">Field Engineers\u2019 Real Feedback: Cables Are Reaching Their Limit In Modern SEA High-Power Projects<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">If you\u2019ve been on-site for recent data center or ESS construction in Malaysia or Vietnam, you\u2019ll notice a clear shift.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Three years ago, almost all low-voltage and DC power distribution relied on cable trays. Today, more EPCs are actively replacing cables with DC busbar trunking \u2014 and it\u2019s not just a trend, it\u2019s a necessity brought by higher rack power density and tropical climate conditions.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Traditional cables work fine for low-power, static-load environments. But for today\u2019s 120kW+ AI racks and cycling battery storage systems, cable bundles create too many hidden problems that only show up after several months of operation.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Power Loss Difference: Cables Waste Far More Energy Under Continuous DC Load<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Tangled multi-core cable bundles naturally create high impedance. When large DC current passes through for 24\/7 continuous operation, heat accumulates unevenly along every cable length.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">We\u2019ve calculated real-site data for Penang data center projects: traditional cable layouts cause 4%\u20136% more annual power loss compared to standard DC busbar systems.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Busbar uses flat, wide T2 copper conductors with extremely uniform current distribution. There are no tangled loops, no concentrated resistance points, so heat generation stays stable and minimal all year round.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Safety &amp; Fire Risk: Cable Aging Is A Major Tropical Hidden Danger<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">High humidity in SEA speeds up cable insulation aging significantly.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Over time, bundled cables trap heat inside the tray, making insulation degrade faster. In worst cases, DC arc faults appear at aging terminals, which is extremely dangerous inside sealed data halls and ESS containers.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Busbar\u2019s fully enclosed metal structure avoids this issue entirely. There are no exposed wiring points, no heat-trapping bundles, and joint temperature can be monitored in real time. For facility safety teams, this makes daily operation far more predictable and secure.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Space Utilization: Cables Block Airflow &amp; Increase PUE<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">One of the biggest pain points operators mention is airflow obstruction.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Layers of cable trays under the raised floor block cold air circulation, forcing cooling systems to work harder and raising overall PUE.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A single set of overhead DC busbar can replace dozens of cable runs. It cleans up the entire aisle layout, improves airflow efficiency, and creates a neater, more maintainable server room environment.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Expansion Flexibility: Cables Kill Project Scalability<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">This is the decisive reason most hyperscale operators switch to busbar.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Cable layout is fixed once installed. If you need to add new racks or upgrade load capacity, you have to re-pull cables, re-terminate, and re-test \u2014 often requiring partial site shutdown.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">With DC busbar, you simply add tap-off boxes on the existing live trunk. No shutdown, no rewiring chaos, no construction delays.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">Real Project Verdict For SEA High-Power Sites<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">For modern AI data centers and MW-level ESS stations in tropical regions, cable-based power distribution is gradually becoming outdated.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">DC busbar delivers lower loss, higher safety, cleaner layout and better scalability \u2014 making it the new standard solution for 2026 and future SEA high-power projects.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Read more\uff1aHigh Efficiency Low-Loss DC Busbar Trunking For SEA Hyperscale Data Center &amp; ESS Projects<\/p>\n","protected":false},"excerpt":{"rendered":"<p>Is DC busbar better than cable for high-power AI data centers and energy storage stations? Full practical comparison for SEA EPC engineers.<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[5],"tags":[],"class_list":["post-896","post","type-post","status-publish","format-standard","hentry","category-industrial-news"],"yoast_head":"<!-- This site is optimized with the Yoast SEO plugin v28.0 - https:\/\/yoast.com\/product\/yoast-seo-wordpress\/ -->\n<title>DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS? | GaoLan TengYuan<\/title>\n<meta name=\"description\" content=\"Comparison between DC busbar trunking and traditional cable wiring on power loss, safety, space saving and expansion flexibility for tropical ESS and data center projects.\" \/>\n<meta name=\"robots\" content=\"index, follow, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n<link rel=\"canonical\" href=\"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/\" \/>\n<meta property=\"og:locale\" content=\"en_US\" \/>\n<meta property=\"og:type\" content=\"article\" \/>\n<meta property=\"og:title\" content=\"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS? | GaoLan TengYuan\" \/>\n<meta property=\"og:description\" content=\"Comparison between DC busbar trunking and traditional cable wiring on power loss, safety, space saving and expansion flexibility for tropical ESS and data center projects.\" \/>\n<meta property=\"og:url\" content=\"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/\" \/>\n<meta property=\"og:site_name\" content=\"GaoLan TengYuan - High &amp; Low Voltage Switchgear Manufacturer | Guangdong Lanteng Electric\" \/>\n<meta property=\"article:publisher\" content=\"https:\/\/facebook.com\" \/>\n<meta property=\"article:published_time\" content=\"2026-07-10T03:28:34+00:00\" \/>\n<meta property=\"article:modified_time\" content=\"2026-07-10T04:59:13+00:00\" \/>\n<meta name=\"author\" content=\"gdltadmin\" \/>\n<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n<meta name=\"twitter:label1\" content=\"Written by\" \/>\n\t<meta name=\"twitter:data1\" content=\"gdltadmin\" \/>\n\t<meta name=\"twitter:label2\" content=\"Est. reading time\" \/>\n\t<meta name=\"twitter:data2\" content=\"3 minutes\" \/>\n<script type=\"application\/ld+json\" class=\"yoast-schema-graph\">{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/#article\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/\"},\"author\":{\"name\":\"gdltadmin\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#\\\/schema\\\/person\\\/6c89168ae14d68bd0562cc41a0a779e3\"},\"headline\":\"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS?\",\"datePublished\":\"2026-07-10T03:28:34+00:00\",\"dateModified\":\"2026-07-10T04:59:13+00:00\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/\"},\"wordCount\":528,\"commentCount\":0,\"publisher\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#organization\"},\"articleSection\":[\"Industrial News\"],\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"CommentAction\",\"name\":\"Comment\",\"target\":[\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/#respond\"]}]},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/\",\"url\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/\",\"name\":\"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers & ESS? | GaoLan TengYuan\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#website\"},\"datePublished\":\"2026-07-10T03:28:34+00:00\",\"dateModified\":\"2026-07-10T04:59:13+00:00\",\"description\":\"Comparison between DC busbar trunking and traditional cable wiring on power loss, safety, space saving and expansion flexibility for tropical ESS and data center projects.\",\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/#breadcrumb\"},\"inLanguage\":\"en-US\",\"potentialAction\":[{\"@type\":\"ReadAction\",\"target\":[\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/\"]}]},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/2026\\\/07\\\/10\\\/dc-busbar-vs-cable-data-center-ess\\\/#breadcrumb\",\"itemListElement\":[{\"@type\":\"ListItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.gltyelectric.com\\\/\"},{\"@type\":\"ListItem\",\"position\":2,\"name\":\"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS?\"}]},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#website\",\"url\":\"https:\\\/\\\/www.gltyelectric.com\\\/\",\"name\":\"Guangdong Lanteng Electric - High & Low Voltage Switchgear Manufacturer\",\"description\":\"Guangdong Lanteng Electric: High &amp; Low Voltage Switchgear and DC Busbar Manufacturer with CE Certification\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#organization\"},\"potentialAction\":[{\"@type\":\"SearchAction\",\"target\":{\"@type\":\"EntryPoint\",\"urlTemplate\":\"https:\\\/\\\/www.gltyelectric.com\\\/?s={search_term_string}\"},\"query-input\":{\"@type\":\"PropertyValueSpecification\",\"valueRequired\":true,\"valueName\":\"search_term_string\"}}],\"inLanguage\":\"en-US\"},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#organization\",\"name\":\"Guangdong Lanteng Electric Co., Ltd.\",\"url\":\"https:\\\/\\\/www.gltyelectric.com\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#\\\/schema\\\/logo\\\/image\\\/\",\"url\":\"https:\\\/\\\/www.gltyelectric.com\\\/wp-content\\\/uploads\\\/2026\\\/04\\\/cropped-GT\u4e2d\u82f1\u6587LOGO.jpg\",\"contentUrl\":\"https:\\\/\\\/www.gltyelectric.com\\\/wp-content\\\/uploads\\\/2026\\\/04\\\/cropped-GT\u4e2d\u82f1\u6587LOGO.jpg\",\"width\":605,\"height\":220,\"caption\":\"Guangdong Lanteng Electric Co., Ltd.\"},\"image\":{\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#\\\/schema\\\/logo\\\/image\\\/\"},\"sameAs\":[\"https:\\\/\\\/facebook.com\",\"https:\\\/\\\/www.youtube.com\",\"https:\\\/\\\/www.linkedin.com\",\"https:\\\/\\\/www.instagram.com\",\"https:\\\/\\\/wa.me\\\/008613711161850\",\"https:\\\/\\\/www.wechat.com\"]},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.gltyelectric.com\\\/#\\\/schema\\\/person\\\/6c89168ae14d68bd0562cc41a0a779e3\",\"name\":\"gdltadmin\",\"image\":{\"@type\":\"ImageObject\",\"inLanguage\":\"en-US\",\"@id\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/a1551e44c973d955595b4d2d01406523b7f13c941ed677b53499e302eeb99490?s=96&d=mm&r=g\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/a1551e44c973d955595b4d2d01406523b7f13c941ed677b53499e302eeb99490?s=96&d=mm&r=g\",\"contentUrl\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/a1551e44c973d955595b4d2d01406523b7f13c941ed677b53499e302eeb99490?s=96&d=mm&r=g\",\"caption\":\"gdltadmin\"},\"sameAs\":[\"http:\\\/\\\/172-237-74-17.ip.linodeusercontent.com\"],\"url\":\"https:\\\/\\\/www.gltyelectric.com\\\/index.php\\\/author\\\/gdltadmin\\\/\"}]}<\/script>\n<!-- \/ Yoast SEO plugin. -->","yoast_head_json":{"title":"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers & ESS? | GaoLan TengYuan","description":"Comparison between DC busbar trunking and traditional cable wiring on power loss, safety, space saving and expansion flexibility for tropical ESS and data center projects.","robots":{"index":"index","follow":"follow","max-snippet":"max-snippet:-1","max-image-preview":"max-image-preview:large","max-video-preview":"max-video-preview:-1"},"canonical":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/","og_locale":"en_US","og_type":"article","og_title":"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers & ESS? | GaoLan TengYuan","og_description":"Comparison between DC busbar trunking and traditional cable wiring on power loss, safety, space saving and expansion flexibility for tropical ESS and data center projects.","og_url":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/","og_site_name":"GaoLan TengYuan - High &amp; Low Voltage Switchgear Manufacturer | Guangdong Lanteng Electric","article_publisher":"https:\/\/facebook.com","article_published_time":"2026-07-10T03:28:34+00:00","article_modified_time":"2026-07-10T04:59:13+00:00","author":"gdltadmin","twitter_card":"summary_large_image","twitter_misc":{"Written by":"gdltadmin","Est. reading time":"3 minutes"},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/#article","isPartOf":{"@id":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/"},"author":{"name":"gdltadmin","@id":"https:\/\/www.gltyelectric.com\/#\/schema\/person\/6c89168ae14d68bd0562cc41a0a779e3"},"headline":"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS?","datePublished":"2026-07-10T03:28:34+00:00","dateModified":"2026-07-10T04:59:13+00:00","mainEntityOfPage":{"@id":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/"},"wordCount":528,"commentCount":0,"publisher":{"@id":"https:\/\/www.gltyelectric.com\/#organization"},"articleSection":["Industrial News"],"inLanguage":"en-US","potentialAction":[{"@type":"CommentAction","name":"Comment","target":["https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/#respond"]}]},{"@type":"WebPage","@id":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/","url":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/","name":"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers & ESS? | GaoLan TengYuan","isPartOf":{"@id":"https:\/\/www.gltyelectric.com\/#website"},"datePublished":"2026-07-10T03:28:34+00:00","dateModified":"2026-07-10T04:59:13+00:00","description":"Comparison between DC busbar trunking and traditional cable wiring on power loss, safety, space saving and expansion flexibility for tropical ESS and data center projects.","breadcrumb":{"@id":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/#breadcrumb"},"inLanguage":"en-US","potentialAction":[{"@type":"ReadAction","target":["https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/"]}]},{"@type":"BreadcrumbList","@id":"https:\/\/www.gltyelectric.com\/index.php\/2026\/07\/10\/dc-busbar-vs-cable-data-center-ess\/#breadcrumb","itemListElement":[{"@type":"ListItem","position":1,"name":"Home","item":"https:\/\/www.gltyelectric.com\/"},{"@type":"ListItem","position":2,"name":"DC Busbar vs Traditional Power Cable: Which Is Better For SEA Data Centers &amp; ESS?"}]},{"@type":"WebSite","@id":"https:\/\/www.gltyelectric.com\/#website","url":"https:\/\/www.gltyelectric.com\/","name":"Guangdong Lanteng Electric - High & Low Voltage Switchgear Manufacturer","description":"Guangdong Lanteng Electric: High &amp; Low Voltage Switchgear and DC Busbar Manufacturer with CE Certification","publisher":{"@id":"https:\/\/www.gltyelectric.com\/#organization"},"potentialAction":[{"@type":"SearchAction","target":{"@type":"EntryPoint","urlTemplate":"https:\/\/www.gltyelectric.com\/?s={search_term_string}"},"query-input":{"@type":"PropertyValueSpecification","valueRequired":true,"valueName":"search_term_string"}}],"inLanguage":"en-US"},{"@type":"Organization","@id":"https:\/\/www.gltyelectric.com\/#organization","name":"Guangdong Lanteng Electric Co., Ltd.","url":"https:\/\/www.gltyelectric.com\/","logo":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/www.gltyelectric.com\/#\/schema\/logo\/image\/","url":"https:\/\/www.gltyelectric.com\/wp-content\/uploads\/2026\/04\/cropped-GT\u4e2d\u82f1\u6587LOGO.jpg","contentUrl":"https:\/\/www.gltyelectric.com\/wp-content\/uploads\/2026\/04\/cropped-GT\u4e2d\u82f1\u6587LOGO.jpg","width":605,"height":220,"caption":"Guangdong Lanteng Electric Co., Ltd."},"image":{"@id":"https:\/\/www.gltyelectric.com\/#\/schema\/logo\/image\/"},"sameAs":["https:\/\/facebook.com","https:\/\/www.youtube.com","https:\/\/www.linkedin.com","https:\/\/www.instagram.com","https:\/\/wa.me\/008613711161850","https:\/\/www.wechat.com"]},{"@type":"Person","@id":"https:\/\/www.gltyelectric.com\/#\/schema\/person\/6c89168ae14d68bd0562cc41a0a779e3","name":"gdltadmin","image":{"@type":"ImageObject","inLanguage":"en-US","@id":"https:\/\/secure.gravatar.com\/avatar\/a1551e44c973d955595b4d2d01406523b7f13c941ed677b53499e302eeb99490?s=96&d=mm&r=g","url":"https:\/\/secure.gravatar.com\/avatar\/a1551e44c973d955595b4d2d01406523b7f13c941ed677b53499e302eeb99490?s=96&d=mm&r=g","contentUrl":"https:\/\/secure.gravatar.com\/avatar\/a1551e44c973d955595b4d2d01406523b7f13c941ed677b53499e302eeb99490?s=96&d=mm&r=g","caption":"gdltadmin"},"sameAs":["http:\/\/172-237-74-17.ip.linodeusercontent.com"],"url":"https:\/\/www.gltyelectric.com\/index.php\/author\/gdltadmin\/"}]}},"_links":{"self":[{"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/posts\/896","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/comments?post=896"}],"version-history":[{"count":2,"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/posts\/896\/revisions"}],"predecessor-version":[{"id":898,"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/posts\/896\/revisions\/898"}],"wp:attachment":[{"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/media?parent=896"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/categories?post=896"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.gltyelectric.com\/index.php\/wp-json\/wp\/v2\/tags?post=896"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}